• No.95 Qilian street, block B, 22F, High-tech Zone,Shijiazhuang City, China, 050000
  • Follow On Social :

GKC433M Circuit Breaker Analyzer

  • Home Products
  • GKC433M Circuit Breaker Analyzer
GKC433M Circuit Breaker Analyzer
  • PB20D Circuit Breaker Control Power Supply
  • PB60D Circuit Breaker Control Power Supply
  • CDF8200A Capacitance and Dissipation Factor (Tan Delta) Tester
  • GI6805 Grounding Connection Device Parameters Tester

GKC433M Circuit Breaker Analyzer

Used to test the mechanical and electrical characteristics of high-voltage circuit breakers, isolating switches, and contactors.

SKU 19
Categories Circuit Breaker Testing

Used to test the mechanical and electrical characteristics of high-voltage circuit breakers, isolating switches, and contactors.

INSTRUCTION

1. Perform mechanical and electrical tests on various high-voltage circuit breakers, isolating switches, and contactors.

2. Test parameters including closing time, opening time, asynchronous time, bounce time, pre-insertion time, and operating (cooperating) time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.

3. Measure the pre-insertion time and resistance of 6 resistor contacts.

4. The instrument interface is equipped with 12 contact status indicators to help determine closing and opening status and verify correct wiring.


FEATURES

1. Perform mechanical and electrical tests on various high-voltage circuit breakers, isolating switches, and contactors.

2. Test parameters including closing time, opening time, asynchronous time, bounce time, pre-insertion time, and operating (cooperating) time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.

3. Measure the pre-insertion time and resistance of 6 resistor contacts.

4. The instrument interface is equipped with 12 contact status indicators to help determine closing and opening status and verify correct wiring.

5. Equipped with one analog transducer input channel and one digital transducer input channel. It measures travel (stroke), penetration, rebound, overshoot time, overshoot, and speed of switchgear using resistive transducers and digital transducers.

6. Digital transducers can accurately measure the rotation angle of single-turn or multi-turn operating mechanisms, with a measurement resolution up to 0.05°. This provides a data basis for judging whether the switch operates correctly.

7. Supports control modes including closing, opening, O-C-O, C-O, and O-C.

8. Capable of testing the mechanical characteristics of manually operated circuit breakers.

9. Supports editing and storing 50 switch models, with user-defined speed settings.

10. Supports modification of speed settings and data recalculation after test completion.

11. Built-in high-power adjustable DC power supply, with a manual voltage adjustment knob, closing button, and opening button. Enables fast closing/opening operation and supply voltage verification.

12. The built-in continuously output DC power supply is used for motor energy storage.

13. Supports motor current measurement. By analyzing the motor current of circuit breakers or isolating switches, it can identify abnormal conditions in the energy storage system or the motion system.

14. Uses electronic switches for output control, with high control accuracy and a long service life.

15. Built-in current sensors measure the current of the closing coils and opening coils.

16. The instrument can store 500 sets of test data, with power-off protection to prevent data loss after power failure.

17. Stored test data can be exported via a USB flash drive.

18. Supports instrument internal software upgrades via a USB flash drive.

19. Equipped with an LCD screen that clearly displays the operation interface, test data, contact waveforms, travel curves, and current curves for both indoor and outdoor use.

21. Equipped with a high-speed thermal printer for printing test data, contact waveforms, travel curves, and current curves.

22. Supports up to 10,000 automatic operation tests.

23. Supports connection to and operation with a computer via a USB communication cable.

24. Test data can be opened on a computer for analysis, envelope generation, and test report creation.

25. Reserved communication interfaces for optional external modules, including dynamic resistance measurement, double-side grounding tests, and graphite contact tests.

26. Supports online testing and internal test data extraction via Bluetooth 2.0 and above devices (optional).


SPECIFICATIONS:

Time Measurement Range: 1~20000 ms. Accuracy: ±(0.05%t + 0.1) ms

1~10000 ms, resolution 0.1 ms; 10000~20000 ms, resolution 0.2 ms

Sampling Frequency: 1~10000 ms: 10 kHz; 10000~20000 ms: 5 kHz

Analog Sensor Input Measurement Range: 0~5 V

Analog Sensor Resistance Range: 50 Ω~5 kΩ

Digital Sensor Interface: Long-distance driver RS422 interface

Digital Sensor Angle Measurement Accuracy: ±0.1°, resolution: 0.05°

Stroke Measurement Range: depends on sensor length; up to 1000 mm. Minimum resolution 0.1 mm

Stroke Measurement Accuracy: ±(0.5%L + 0.2) mm

Speed Measurement Range: 0~20 m/s, resolution 0.01 m/s

DC Power Supply Output: 10~270 V/20 A, power 3 kW

DC Voltmeter Measurement Range: 0~300 V, accuracy: ±(0.5%U + 1) V

Coil Current Measurement: DC 0~3 A~30 A; AC peak 0~3 A~30 A; resolution: 0.01 A

Motor Current Measurement: DC 0~4 A~40 A; AC peak 0~4 A~40 A; resolution: 0.01 A

Closing Resistor Measurement Range: 50~2000 Ω; resolution: 0.1 Ω; accuracy: ±(1%R + 1) Ω

Trigger Start Voltage: ≥30 V

Output Control Power: 300 V DC/AC, 30 A DC/AC

Power Supply: 198~264 V AC, 47~63 Hz

Operating Conditions: Temperature -10℃~50℃, Humidity ≤90% RH, non-condensing

Dimensions: 427 mm × 357 mm × 193 mm

Weight: 9 kg