In power systems, earth-net ground resistance is mainly measured using the power-frequency, high-current method, where the test current must be not less than 30 A to avoid grid-generated frequency interference and improve test accuracy. This approach results in cumbersome equipment, a complex test process, and long test times.
| SKU | 22 |
| Categories | Grounding Connection Device Parameters Tester |
In power systems, earth-net ground resistance is mainly measured using the power-frequency, high-current method, where the test current must be not less than 30 A to avoid grid-generated frequency interference and improve test accuracy. This approach results in cumbersome equipment, a complex test process, and long test times.
INSTRUCTION:
At present, in power systems, the earth net ground resistance is mainly tested using the power-frequency high-current method. To prevent frequency interference generated by the operation of the power grid and to improve the accuracy of test results, the test procedure stipulates that the test current of the power-frequency high-current method shall not be less than 30 A. As a result, such test equipment is cumbersome, the testing process is complex, the test duration is long, and there are other drawbacks.
The HANDY Grounding Connection Device Parameter Tester uses a new type of variable-frequency AC power supply and abandons the traditional frequency transformer design, significantly reducing the instrument weight. With digital signal processing technology, it avoids 50 Hz frequency interference, enabling measurement without power interruption and improving the accuracy of the test results. Overall, the test process is greatly simplified.
This instrument is suitable for testing the ground resistance of various grounding devices, including touch potential, step potential, voltage gradients, and soil resistivity. It supports multiple application scenarios, including measurement in substation grounding grids (4 Ω), hydrothermal power plants, microwave stations (10 Ω), and lightning rods (10 Ω).
FEATURES:
1. Accurately measure parameters such as ground impedance, ground resistance, voltage gradient, touch potential, step potential, soil resistivity, etc., to meet conventional grounding network parameter measurement requirements.
2. The test power supply provides an interfrequency power supply close to the target frequency, enabling effective separation of frequency components from interference and ensuring reliable measurement of small signals.
3. High testing accuracy; suitable for measuring grounding meshes with very low ground impedance.
4. The all-electronic, non-working frequency transformer design is compact and lightweight, making it easy to carry.
5. The instrument automatically completes power boosting control and data measurement/calculation; testing time is short and workload is reduced.
6. Current and voltage waveforms can be saved, and test data can be analyzed using the upper computer software.
7. The LCD screen provides clear display both indoors and outdoors, showing the operating interface and test data.
8. Built-in large-capacity memory stores up to 1000 sets of data and retains data when power is off.
9. A high-speed thermal printer prints test data.
10. Upgrade instrument software via a USB flash drive.
SPECIFICATIONS:
1. Power supply: Three-phase 380 V ±10%, 47–63 Hz; Power: 30 kVA
2. Output voltage: 0–400 V (RMS)
3. Output current: 0–50 A (RMS)
4. Testing time: 30 s
5. Testing power frequency: 42–58 Hz; multi-frequency measurement
6. Measurement range: 0–100 Ω; Resolution: 1 mΩ
7. Measurement accuracy: ±(1% ± 5 mΩ)
8. Anti-jamming capability: Instrument output signal-to-interference signal ratio can be maintained steadily and accurately at 1:50.
9. Dimension: 613 mm × 488 mm × 234 mm
10. Working environment: T: -20 to 50 °C; H ≤ 90% RH
11. Weight: 39 kg