CTC760E Instrument Transformer Analyzer

CTC760E instrument transformer analyzer performs standard tests quickly, including magnetization characteristic, saturation behavior (ALF/FS), transformation ratio and accuracy, polarity, load, winding resistance, and remanence. Testing is conducted in accordance with IEC 60044-1, IEC 60044-6, IEC 61869, and ANSI/IEEE C57.13.1.

SKU 18
Categories Instrument Transformer Testing

CTC760E instrument transformer analyzer performs standard tests quickly, including magnetization characteristic, saturation behavior (ALF/FS), transformation ratio and accuracy, polarity, load, winding resistance, and remanence. Testing is conducted in accordance with IEC 60044-1, IEC 60044-6, IEC 61869, and ANSI/IEEE C57.13.1.

FEATURES:

Uses a direct-current (DC) test method and a variable-frequency (low-frequency) test method for CTs.

Excitation characteristic testing below 80 kV is available, with fast operation.

Supports both the “voltage method” (via secondary injection) for testing the current transformer (CT) ratio and polarity, including CTs integrated in transformer bushings.

The built-in power supply provides an output in current mode. It can be used to test CT ratio and polarity and to verify the integrity of the CT secondary circuit.

Output up to 200 A with an external current booster (option).

Tests the DC resistance of the CT secondary winding.

Tests the burden of the CT secondary circuit.

Tests voltage transformer excitation characteristics, ratio, polarity, and secondary winding DC resistance.

Draws the excitation curve and determines the knee point in accordance with IEC 60044-1 and IEC 60044-6.

Draws CT error curves at 5% and 10%.

Measures CT ratio error and phase displacement.

Measures CT remanence factor (Kr), magnetizing inductance (Lm), secondary loop time constant (Ts), transient dimensioning factor (Ktd), peak instantaneous error (PIE), accuracy limit factor (ALF), and instrument security factor (FS).

Draws the current transformer hysteresis loop curve.

Transparent display clearly shows values and curves both indoors and outdoors.

High-speed thermal printer prints values and curves.

Automatically checks the connecting cable. Provides wrong-connection warning instructions.

Built-in large-capacity memory stores up to 20,000 winding test values; power loss does not result in loss of stored values.

Uses a USB flash drive to transfer test values to a PC and generate reports.

Uses a USB flash drive to update software.

 

SPECIFICATIONS:

Output Voltage: 0–360 V AC

Output Current: 0–10 A rms, peak 20 A

External Current Booster Output Current: 0–200 A AC

External Current Booster Output Current Duration: 8 min at 150 A

Output Power: 0–3600 VA

Secondary Voltage Measurement Range: 2–360 V AC

Secondary Voltage Measurement Accuracy: ±(0.1% U + 20 mV)

Primary Voltage Measurement Range: 0–20 V AC

Output Current Measurement Range: 0.01–10 A AC

Output Current Measurement Accuracy: ±(0.1% I + 2 mA)

Secondary Current Measurement Range: 0–5 A AC

Secondary Current Measurement Accuracy: ±(0.1% I + 2 mA)

Winding Resistance Measurement Range: 0–300 Ω, resolution 1 mΩ

Winding Resistance Measurement Accuracy: ±(0.1% R + 1 mΩ)

AC Burden Load Measurement: 0–1000 VA, resolution 0.001 VA

Transformation Ratio Measurement Range: 1–35000

Rated Current Transformation Ratio Error: ±0.1% for 1–5000; ±0.2% above 5000

Rated Current Phase Error: 3 min at cosφ = 0.8–1; resolution 0.1 min

Power Supply: 198–264 V AC, 47–63 Hz

Operating Conditions: Temperature −10°C to 50°C; Humidity ≤ 90% RH (non-condensing)

Main Unit Dimensions: 427 × 357 × 193 mm

Main Unit Weight: 11 kg

Current Booster Dimensions: 327 × 282 × 218 mm