• No.95 Qilian street, block B, 22F, High-tech Zone,Shijiazhuang City, China, 050000
  • Follow On Social :

ZD1C Contact Resistance Tester

  • Home Products
  • ZD1C Contact Resistance Tester
ZD1C Contact Resistance Tester
  • PB20D Circuit Breaker Control Power Supply
  • PB60D Circuit Breaker Control Power Supply
  • CDF8200A Capacitance and Dissipation Factor (Tan Delta) Tester
  • GI6805 Grounding Connection Device Parameters Tester

ZD1C Contact Resistance Tester

As distribution networks carry heavier loads, the risk of overheating increases; measuring contact resistance at regular intervals helps detect faults before they cause overheating. The contact resistance tester measures contact resistances of circuit breakers, disconnecting switches, earthing switches, bus joints, bushing contact joints, and welding joints, and is also suitable for other low-resistance measurement applications. It provides 100 A DC current, measures the test object voltage, and

SKU 21
Categories Resistance Measurement

As distribution networks carry heavier loads, the risk of overheating increases; measuring contact resistance at regular intervals helps detect faults before they cause overheating. The contact resistance tester measures contact resistances of circuit breakers, disconnecting switches, earthing switches, bus joints, bushing contact joints, and welding joints, and is also suitable for other low-resistance measurement applications. It provides 100 A DC current, measures the test object voltage, and

FEATURES:

Set the output current test duration between 1 s and 60 s.
Store the device series number for convenient result checking.
Display output current, output time, and resistance during testing.
Store up to 100 test results in the tester memory.
Built-in clock records the date.
The stored result includes the device number, testing time, and resistance.

SPECIFICATIONS:

Test current: 100 A

Output power: 1 kW

Measuring range: 0.1 μΩ to 20000 μΩ

Accuracy: ± 0.5% rdg ± 0.2 μΩ

Range 0.1 μΩ to 999.9 μΩ,
Resolution: 0.1 μΩ
Range 1000 μΩ to 20000 μΩ,
Resolution: 1 μΩ

Ammeter accuracy:

± 0.5% rdg ± 0.1 A

Dimensions: 403 × 330 × 178 mm

Weight: 7 kg

General

Memory capacity: 100 results

Power supply: 198 to 264 VAC
47 to 63 Hz

Environment: -20 to 50 ℃
Humidity ≤ 90% RH, non-condensing