Measures the resistance of circuit breaker contacts, switchgear contacts, and bus-bar joints. Resistance is calculated using Ohm’s law (R = U/I).
FEATURES:
1. Adjustable output timing from 1 s to 60 s. 2. Allows entry of the device number for convenient result verification. 3. Displays the present current, test time, and resistance during testing. 4. Stores up to 500 test results. 5. Built-in clock for recording the date. 6. Stored results include the device number, testing time, and resistance.
SPECIFICATIONS:
DC Output current: 100 A / 200 A Output power: 100 A: 1000 VA 200 A: 2000 VA Measuring range: 100 A: 1 μΩ to 20 mΩ 200 A: 1 μΩ to 10 mΩ Resolution: 0.1 to 999.9 μΩ (resolution: 0.1 μΩ) 1 mΩ to 10 mΩ (resolution: 1 μΩ) 10 mΩ to 20 mΩ (resolution: 10 μΩ) Accuracy class: ± (0.5%R + 0.2 μΩ) Ammeter accuracy: ± (0.5%I + 0.1) A Power supply: AC 188 V to 242 V, 47 Hz to 63 Hz Operating environment: -10℃ to 40℃; Humidity: ≤85% RH Dimensions: 403 mm × 330 mm × 178 mm; Weight: 8 kg
Measures the resistance of circuit breaker contacts, switchgear contacts, and bus-bar joints. Resistance is calculated using Ohm’s law (R = U/I).
FEATURES:
1. Adjustable output timing from 1 s to 60 s.
2. Allows entry of the device number for convenient result verification.
3. Displays the present current, test time, and resistance during testing.
4. Stores up to 500 test results.
5. Built-in clock for recording the date.
6. Stored results include the device number, testing time, and resistance.
SPECIFICATIONS:
DC Output current: 100 A / 200 A
Output power: 100 A: 1000 VA
200 A: 2000 VA
Measuring range: 100 A: 1 μΩ to 20 mΩ
200 A: 1 μΩ to 10 mΩ
Resolution: 0.1 to 999.9 μΩ (resolution: 0.1 μΩ)
1 mΩ to 10 mΩ (resolution: 1 μΩ)
10 mΩ to 20 mΩ (resolution: 10 μΩ)
Accuracy class: ± (0.5%R + 0.2 μΩ)
Ammeter accuracy: ± (0.5%I + 0.1) A
Power supply: AC 188 V to 242 V, 47 Hz to 63 Hz
Operating environment: -10℃ to 40℃; Humidity: ≤85% RH
Dimensions: 403 mm × 330 mm × 178 mm; Weight: 8 kg