Power-frequency parameters of long-distance EHV and UHV transmission lines are essential for power system modelling and analysis. However, accurate measurement is particularly difficult because the line behaviour is dominated by reactance and is affected by strong external interference.
| SKU | 20 |
| Categories | Transmission Line Parameter Testing |
Power-frequency parameters of long-distance EHV and UHV transmission lines are essential for power system modelling and analysis. However, accurate measurement is particularly difficult because the line behaviour is dominated by reactance and is affected by strong external interference.
INSTRUCTION:
Power-frequency parameters of long-distance extra-high-voltage (EHV) and ultra-high-voltage (UHV) transmission lines are the basis for power system modelling and analysis; however, these parameters are especially difficult to measure accurately due to reactance-dominated characteristics and strong external interference.
The HANY LPT15 series transmission line analyzer uses a new variable-frequency technical method to measure these parameters.
The LPT15 series transmission line analyzer is suitable for measuring power-frequency parameters of overhead lines and cables, including line phase checking and DC resistance measurement.
The analyzer features an all-in-one design based on an all-electronic non-working frequency transformer, offering advantages of small size, light weight, and convenient portability compared with the traditional inverter and frequency transformer structure found in the market.
The unique absorption feedback circuit technical enables the tester to withstand 10 to 100 A of induced current without requiring an anti-jamming suppression device.
The unique three-phase parallel output mode enables zero-sequence impedance measurement, achieving three times the induced current capability of a single-phase output mode.
Based on the variable-frequency test principle, and using hardware and digital filtering technology together with Fourier transformation technology, the instrument performs accurate measurements.
The LPT15 series integrated tester for frequency line parameters is an ideal embodiment of modern power electronics and signal-processing technology.
FEATURES:
1. Using a variable method to accurately measure positive-sequence short-circuit impedance, positive-sequence open-circuit impedance (positive-sequence capacitor), zero-sequence short-circuit impedance, and zero-sequence open-circuit impedance (zero-sequence capacitor), as well as the coupling inductor (mutual inductor), coupling capacitor, and induced current.
2. Using the DC power method to check line phases.
3. Measuring line DC resistance and converting the measured value to the corresponding temperature reference.
4. Measuring induced voltage. A voltage divider is required when the induced voltage exceeds 750 V.
5. Built-in Bluetooth: operate the analyzer via Bluetooth using a mobile phone or tablet for improved safety. (Option)
6. The analyzer adopts an all-in-one design based on an all-electronic non-working frequency transformer, featuring small size, light weight, and convenient portability.
7. One-time connection enables phase verification, DC resistance measurement, and line parameter testing in a single setup. This improves work efficiency and helps avoid risks caused by re-connection.
8. A combination of hardware and software anti-jamming measures provides anti-frequency interference capacity up to 1000 times.
9. Zero-sequence impedance measurement uses a three-phase parallel output mode, providing induced current withstand capability three times higher than the single-phase output mode.
10. No additional anti-jamming suppression device is required. Depending on the model, the analyzer can withstand induced current from 10 A to 100 A.
11. Automatic boosting voltage, measurement, lowdown voltage, and calculation to save test time.
12. Save current and voltage curves and transfer analysis results to a computer.
13. Built-in large-capacity memory stores 1024 sets of data and retains data even in the event of power loss.
14. Use a USB drive to transfer test data and perform software upgrades.
15. The operating interface and test data are displayed on the LCD screen, ensuring clear visibility both indoors and outdoors.
16. High-speed thermal printers for printing test data.
17. Power input overvoltage protection (>270 V AC).
18. Provides an ungrounded prompt function for the instrument.
SPECIFICATIONS:
1. Power supply: single-phase AC 198~264 V, 47~63 Hz; power: 5 kVA
2. Output voltage: three-phase, 0~200 V (RMS)
3. Output current: three-phase, 0~10 A (RMS)
4. Test frequency: 42~58 Hz
5. Capacitance measurement range: 0.1~30 μF; resolution: 0.01 μF
Accuracy (reference/typical as stated): 0.1~1 μF ±(3%·C + 0.01 μF); 1~50 μF ±(1%·C + 0.01 μF)
6. Resistance measurement range: 0.5~400 Ω; resolution: 0.01 Ω
Accuracy (reference/typical as stated): 0.5~1 Ω ±(3%·Z + 0.01 Ω); 1~400 Ω ±(1%·Z + 0.01 Ω)
7. Impedance angle measurement range: 0~360°; resolution: 0.01°
Accuracy (reference/typical as stated): ±0.3°
8. DC resistance measurement range: 0.02~60 Ω; resolution: 0.1 mΩ
Accuracy (reference/typical as stated): ±(0.2%·R + 0.2 mΩ) (The equipment will output current of 2 A to 4 A depending on the resistance.)
9. Voltage measurement range: 10~750 V; accuracy: ±(0.5%·U + 0.2 V)
10. Current measurement range: 0.5~20 A; accuracy: ±(0.5%·I + 0.02 A)
11. Rated/withstand induced voltage: <30 kV
12. Rated/withstand induced current: per phase 100 A; zero-sequence 300 A
13. Dimensions: 613×488×341 mm
14. Weight: 36.1 kg
15. Environmental conditions: T: -20~50°C; H ≤ 90% RH